Products

Mitsubishi input module FX2N-8AD

Mitsubishi input module FX2N-8AD analog input (temperature sensor input) module features:
1) FX2N-8AD resolution is 14-bit binary + 1-bit sign (voltage) 13-bit binary + 1-bit sign (current) Analog input module

Send Inquiry

Product Description

brand MITSUBISHI/Japan Mitsubishi
Origin category import

Features of Mitsubishi input module FX2N-8AD analog input ( temperature sensor input ) module:

 1) FX2N-8AD is an analog input module with a resolution of 14 -bit binary + 1- bit sign ( voltage ), 13 -bit binary + 1- bit sign ( current )

2) FX2N-8AD can provide 8 channels of voltage input (DC-10~10V) current input (DC4~ 20mA , DC-20~20mA) and thermocouple (K type, J type, T type ) input

3) FX2N-8AD can be used in units of channels and mixed use of voltage and current thermocouple inputs.

4) Up to two FX2N-8AD units can be connected to the FX0N main unit , FX0N expansion unit , and FX1N main unit . Up to 8 FX2N -8AD can be connected to one FX2N series PLC, and up to 4 FX2N-8AD can be connected to one FX2NC . Host unit . ( To connect to the FX2NC series host , an FX2NC-CNV-1F is required)

 

Mitsubishi input module FX2N-8AD other specifications and performance:

Suitable specifications

CE (EMC), UL/cUL, KC, GL, BV, RINA, NK

Performance specifications

Analog input

Analog input range

Input voltage

DC - 10 V ~ + 10 V (input resistance 200 kΩ)

Input Current

DC - 20 mA~20 mA, 4 mA~20 mA (input resistance 250Ω)

Enter channel

Channel 8

absolute maximum input

Input voltage

±15 V

Input Current

±30mA

Input properties

For each channel, the input mode (voltage/input current) can be set.

Diguido output

Input voltage

14 bit signed binary + 1 bit

Input Current

13 bit symbol binary + 1 bit

resolution

Input voltage

0.63 mV (20 V × 1 / 32000)

2.50 mV (20 V×1/8000)

Input Current

- 20 ~+20 mA: 5.00μA (40 mA×1/8000), 2.50μA (40 mA×1/16000)

+ 4 ~ + 20 mA: 4.00μA (16 mA×1/4000), 2.00μA (16 mA×1/8000)

Comprehensive accuracy

Input voltage

Ambient temperature 25℃±5℃: Full scale 20 V vs. ±0.3% (±60 mV)

Ambient temperature 0℃~55℃: full scale 20 V vs. ±0.5% (±100 mV)

Input Current] [

Ambient temperature 25℃±5℃: Full scale 40mA vs. ±0.3% (±120μA), +4mA ~ 20mA input is the same (±120μA)

Ambient temperature 0℃~55℃: Full scale 40mA vs. ±0.5% (±200μA), +4mA~20mA input is the same (±200μA)

A/D conversion time

500 μs × channel used

Insulation method

Analog input section and during sequence, photocoupler is more insulated than

The DC/DC converter is insulated between the analog input section and the power supply

· Each channel is not insulated

temperature sensor, temperature

input signal

Thermocouple K type, J type, T type

Differences in channels per K-type, J-type, T-type possible

Enter channel

Channel 8

Rated temperature range

type] [

- 100  ~ 1200  (- 148 °F ~ 2192 F)

Type] [ J

- 100  ~ 600  (- 148 °F ~ 1112°F)

type] [

- 100  ~ 350  (- 148 °F ~ 662°) F

Diguido output

type] [

- 1000 ~12000 (- 1480~21920)

Type] [ J

- 1000 ~6000 (- 1480~11120)

type] [

- 1000 ~3500 (- 1480~6620)

( ), Diguido value when set in Fahrenheit

resolution

type] [

0.1 ℃ (0.1 °F )

Type] [ J

0.1 ℃ (0.1 °F )

type] [

0.1 ℃ (0.1 °)F

Comprehensive accuracy, measurement accuracy

type] [

Ambient temperature 0℃~55℃: ±0.5% of full scale

±6.5℃/±11.7°F)

Type] [ J

Ambient temperature 0℃~55℃: ±0.5% of full scale

±3.5℃/±6.3°F)

type] [

Ambient temperature 0℃~55℃: ±0.7% of full scale

±3.15℃/±5.67°) F

control method

according to sequence procedure

Action when input is disconnected/short-circuited

When using the thermocouple input method, only the disconnection detection function is available (equipped with V 1.10 or later of FX 2 N - 8 AD)

action sequence program

conversion speed

Input [voltage, current input only when used]

500 μs × channel used

When using thermocouple input channel [1] or above

The input voltage and current input channels are one ms × the channel used.

Thermocouple input uses channel 40 ms × channel

(Using channel, input voltage, current input, thermocouple input using all channel score table)

Insulation method

Analog input section and during sequence, photocoupler is more insulated than

The DC/DC converter is insulated between the analog input section and the power supply

· Each channel is not insulated

Input and output share score

o'clock (input or output can be any countdown)

Applicable sequence

FX 2 N, FX 3 U, FX 2 NC, FX 3 UC

"Connector Type Serializer Connected to About>

FX 2 CNC access, FX 2 NC-CNV-IF is necessary.

A connection of FX 3 UC, FX 2 NC - CNV - IF or FX 3 UC - 1 PS - 5V is necessary.

quality

0.4kg