Mitsubishi input module FX2N-8AD analog input (temperature sensor input) module features:
1) FX2N-8AD resolution is 14-bit binary + 1-bit sign (voltage) 13-bit binary + 1-bit sign (current) Analog input module
1) FX2N-8AD is an analog input module with a resolution of 14 -bit binary + 1- bit sign ( voltage ), 13 -bit binary + 1- bit sign ( current )
2) FX2N-8AD can provide 8 channels of voltage input (DC-10~10V) current input (DC4~ 20mA , DC-20~20mA) and thermocouple (K type, J type, T type ) input
3) FX2N-8AD can be used in units of channels and mixed use of voltage and current thermocouple inputs.
4) Up to two FX2N-8AD units can be connected to the FX0N main unit , FX0N expansion unit , and FX1N main unit . Up to 8 FX2N -8AD can be connected to one FX2N series PLC, and up to 4 FX2N-8AD can be connected to one FX2NC . Host unit . ( To connect to the FX2NC series host , an FX2NC-CNV-1F is required)
Mitsubishi input module FX2N-8AD other specifications and performance:
Suitable specifications |
CE (EMC), UL/cUL, KC, GL, BV, RINA, NK |
||
Performance specifications |
Analog input |
Analog input range |
Input voltage |
DC - 10 V ~ + 10 V (input resistance 200 kΩ) |
|||
Input Current |
|||
DC - 20 mA~20 mA, 4 mA~20 mA (input resistance 250Ω) |
|||
Enter channel |
Channel 8 |
||
absolute maximum input |
Input voltage |
||
±15 V |
|||
Input Current |
|||
±30mA |
|||
Input properties |
For each channel, the input mode (voltage/input current) can be set. |
||
Diguido output |
Input voltage |
||
14 bit signed binary + 1 bit |
|||
Input Current |
|||
13 bit symbol binary + 1 bit |
|||
resolution |
Input voltage |
||
0.63 mV (20 V × 1 / 32000) |
|||
2.50 mV (20 V×1/8000) |
|||
Input Current |
|||
- 20 ~+20 mA: 5.00μA (40 mA×1/8000), 2.50μA (40 mA×1/16000) |
|||
+ 4 ~ + 20 mA: 4.00μA (16 mA×1/4000), 2.00μA (16 mA×1/8000) |
|||
Comprehensive accuracy |
Input voltage |
||
Ambient temperature 25℃±5℃: Full scale 20 V vs. ±0.3% (±60 mV) |
|||
Ambient temperature 0℃~55℃: full scale 20 V vs. ±0.5% (±100 mV) |
|||
Input Current] [ |
|||
Ambient temperature 25℃±5℃: Full scale 40mA vs. ±0.3% (±120μA), +4mA ~ 20mA input is the same (±120μA) |
|||
Ambient temperature 0℃~55℃: Full scale 40mA vs. ±0.5% (±200μA), +4mA~20mA input is the same (±200μA) |
|||
A/D conversion time |
500 μs × channel used |
||
Insulation method |
・Analog input section and during sequence, photocoupler is more insulated than |
||
・The DC/DC converter is insulated between the analog input section and the power supply |
|||
· Each channel is not insulated |
|||
temperature sensor, temperature |
input signal |
Thermocouple K type, J type, T type |
|
Differences in channels per K-type, J-type, T-type possible |
|||
Enter channel |
Channel 8 |
||
Rated temperature range |
K type] [ |
||
- 100 ℃ ~ 1200 ℃ (- 148 °F ~ 2192 F) |
|||
Type] [ J |
|||
- 100 ℃ ~ 600 ℃ (- 148 °F ~ 1112°F) |
|||
T type] [ |
|||
- 100 ℃ ~ 350 ℃ (- 148 °F ~ 662°) F |
|||
Diguido output |
K type] [ |
||
- 1000 ~12000 (- 1480~21920) |
|||
Type] [ J |
|||
- 1000 ~6000 (- 1480~11120) |
|||
T type] [ |
|||
- 1000 ~3500 (- 1480~6620) |
|||
( ), Diguido value when set in Fahrenheit |
|||
resolution |
K type] [ |
||
0.1 ℃ (0.1 °F ) |
|||
Type] [ J |
|||
0.1 ℃ (0.1 °F ) |
|||
T type] [ |
|||
0.1 ℃ (0.1 °)F |
|||
Comprehensive accuracy, measurement accuracy |
K type] [ |
||
Ambient temperature 0℃~55℃: ±0.5% of full scale |
|||
( ±6.5℃/±11.7°F) |
|||
Type] [ J |
|||
Ambient temperature 0℃~55℃: ±0.5% of full scale |
|||
( ±3.5℃/±6.3°F) |
|||
T type] [ |
|||
Ambient temperature 0℃~55℃: ±0.7% of full scale |
|||
( ±3.15℃/±5.67°) F |
|||
control method |
according to sequence procedure |
||
Action when input is disconnected/short-circuited |
When using the thermocouple input method, only the disconnection detection function is available (equipped with V 1.10 or later of FX 2 N - 8 AD) |
||
action sequence program |
|||
conversion speed |
Input [voltage, current input only when used] |
||
500 μs × channel used |
|||
When using thermocouple input channel [1] or above |
|||
The input voltage and current input channels are one ms × the channel used. |
|||
Thermocouple input uses channel 40 ms × channel |
|||
(Using channel, input voltage, current input, thermocouple input using all channel score table) |
|||
Insulation method |
・Analog input section and during sequence, photocoupler is more insulated than |
||
・The DC/DC converter is insulated between the analog input section and the power supply |
|||
· Each channel is not insulated |
|||
Input and output share score |
8 o'clock (input or output can be any countdown) |
||
Applicable sequence |
FX 2 N, FX 3 U, FX 2 NC, FX 3 UC |
||
"Connector Type Serializer Connected to About> |
|||
FX 2 CNC access, FX 2 NC-CNV-IF is necessary. |
|||
A connection of FX 3 UC, FX 2 NC - CNV - IF or FX 3 UC - 1 PS - 5V is necessary. |
|||
quality |
0.4kg |