Mitsubishi module FX2N-48ER-D

Mitsubishi module FX2N-48ER-D function introduction:
1 Input and output expansion unit
2 Input and output 24:24, expansion is possible.
3 The power supply is built-in, and various input and output devices and special

Send Inquiry

Product Description

brand MITSUBISHI/Japan Mitsubishi
Origin category import

Mitsubishi module FX2N-48ER-D function introduction:
1  input and output expansion unit
2  input and output 24:24, expansion is possible.
3.  The power supply is built-in, and various input and output devices and special additions are also added to the second half of the basic unit and the same extension unit Can connect.

Mitsubishi module FX2N-48ER-D other performance:

category Input and output expansion
Product name expansion unit
Performance specifications Applicable sequence FX3G, FX2N, FX3U
quality 0.85kg
General specifications ambient temperature 0 ~ 55℃·····When operating - 25~75℃·····When saving
Relative humidity 5~95% RH (no condensation allowed)・・・・・When operating
Vibration resistant When installing on DIN rail Piece amplitude: 0.035 mm 10 times in each direction of X, Y, and Z (a total of 80 minutes) each
Judgment criteria, based on IEC 61131-2
When installing on DIN rail Acceleration: 4.9 m/s 2 10 times in each direction of X, Y and Z (80 minutes in total)
Judgment criteria, based on IEC 61131-2
When installing directly Piece amplitude: 0.075 mm 10 times in each direction of X, Y, Z (a total of 80 minutes) each
Judgment criteria, based on IEC 61131-2
When installing directly Acceleration: 9.8 m/s 2 10 times in each direction of X, Y and Z (80 minutes in total)
Judgment criteria, based on IEC 61131-2
Shock proof 147 m/s2 , action time 11 ms, sine half-wave pulse 3 times in each direction of X, Y, Z
Judgment criteria, based on IEC 61131-2
Noise resistant Noise voltage, Vp 10,000-p, noise width 1μs, rising to one, period 30 ~ 100 Hz of the noise simulator
Withstand voltage Between power terminal (DC power supply) and ground terminal: AC 500 V for 1 minute
Between input terminal (DC 24V) and ground terminal: AC 500 V for 1 minute
Between output terminal (torch transmission) and ground terminal: AC 1500 V for 1 minute
Insulation resistance Between each terminal and the ground terminal: DC 500 V high resistance meter above 5 MΩ
ground Type D grounding (ground resistance: 100Ω or less)
Ground, dedicated ground or shared ground, please.
Atmosphere of use Corrosive, flammable gases, but conductive dust (dust) are very unsafe
Use height Below 2000 meters
It cannot be used in a pressurized environment above atmospheric pressure. Possibility of malfunction.
Power Specifications Rated voltage DC24V
Voltage allowable range + 20%, - 30%
Mains fuse 250 VA 5
Consumption of electricity 30W
Enter specifications Enter score 24 o'clock
Enter the connection shape Removable terminal block (M) 3 screws
Input form heat sink
Input signal voltage DC 24V + 20%, - 30%
input resistance 4.3 kΩ
Input signal current 5mA/DC 24V
Input current ON sensitivity 3.5mA or more
Input current OFF sensitivity Below 1.5 mA
Enter response time about 10 ms
Input signal form Wireless voltage solder joint input or NPN transistor open collector
Input circuit isolation Optocoupler insulation
Input action representation The LED on the panel lights up when the input is ON.
Output specifications Output score 24 o'clock
Output connection shape Removable terminal block (M) 3 screws
Output type/form relay
External power supply AC 250 V DC 30 V or less
maximum load Resistive load 2 A / 1 point
Please see below for the total load current in the UK.
and output 4 points/Eng: 8 A or less
and output 8 points/Eng: 8 A or less
inductive load 80VA
minimum load DC5V 2mA (reference value)
Response time Discount→ON about 10 ms
ON→Discount about 10 ms
circuit insulation mechanical insulation
Output action representation When the relay coil is energized, the LED on the panel lights up.
Output circuit structure