Products

Mitsubishi UPS FW-V Series

Mitsubishi's FW-V series (100V type) had its order acceptance end in May 2019. Additionally, specific models including FW-V20-1.0K, FW-VEB-01, and FW-V2CB-01 had their order acceptance end in June 2023.

 

FW-V-2.png


This text provides detailed specifications for the Mitsubishi FW-V Series UPS (Uninterruptible Power Supply) models, including both 100V and 200V types. Here are the key points:

 

100V Tower Type FREQUPS (FW-V10 Series)

 

  • Models: FW-V10-0.7K, FW-V10-1.0K, FW-V10-1.5K, FW-V10-2.0K, FW-V10-3.0K, FW-V10-5.0K
  • Input: Single-phase 2-wire (AC85V~144V), power factor ≥0.95
  • Output: Single-phase 2-wire, voltage 100V~120V ±2%, capacity up to 5.0kVA/3.5kW
  • Battery: Sealed lead-acid battery, 5-year lifespan, 10 minutes backup time at full load
  • Features: True sine wave output, seamless switchover during power loss, overload protection (110% for 30 sec, 140% for 3 sec), fan-cooled, RS-232C interface, low noise (45dB or less)

 

100V Rack Type FREQUPS (FW-V10R Series)

 

  • Models: FW-V10R-1.5K, FW-V10R-3.0K
  • Input: Single-phase 2-wire (AC85V~144V), power factor ≥0.95
  • Output: Single-phase 2-wire, voltage 100V~120V ±2%, capacity up to 3.0kVA/2.1kW
  • Battery: Similar to tower models with 10-minute backup time
  • Features: Includes rack-mount design, true sine wave output, seamless switchover, RS-232C interface, and fan cooling

 

200V Series FREQUPS (FW-V20 Series)

 

  • Models: FW-V20-1.0K, FW-V20-3.0K, FW-V20-5.0K
  • Input: Single-phase 2-wire (AC200V~240V), power factor ≥0.95
  • Output: Single-phase or three-wire, voltage 200V240V or 100V120V, capacity up to 5.0kVA/3.5kW
  • Battery: Sealed lead-acid, 5-year lifespan, 10-minute backup
  • Features: True sine wave output, seamless switchover, RS-232C interface, low noise (45dB), and optional external battery expansion

 

General Notes:

 

  1. UPS models feature surge protection, peak current handling up to 300% of rated capacity, and overload protection.
  2. External interfaces include RS-232C and slots for optional expansion boards.
  3. For some models, an external step-down transformer is required to handle capacities 1.5 times the UPS rating.
  4. The 200V series should not be connected to half-wave rectified loads.

 

This information is useful for selecting and configuring the appropriate UPS model based on capacity and input/output needs, ensuring proper handling of power surges, and backup requirements.

 

View as  
 
  • 3.0kVA / 2.1kW Rack-Mount Online UPS | 100V SystemThe Mitsubishi FW-V10R-3.0K is a high-reliability, rack-mount uninterruptible power supply (UPS) designed for 100V-class critical power environments. As part of the FREQUPS FW-V Series, this 4U UPS unit provides true online double-conversion technology, delivering uninterrupted, high-quality power to mission-critical systems such as servers, industrial controllers, and communications infrastructure.With an output capacity of 3.0kVA / 2.1kW, the FW-V10R-3.0K offers seamless switchover during outages (0ms transfer time), pure sine wave output, and dual output options (NEMA 5-15R outlets + terminal block). It also features RS-232C communication and external signal integration for advanced monitoring and control.

  • The Mitsubishi FW-V10R-1.5K is a compact rack-mounted UPS designed to deliver uninterrupted, high-quality power to mission-critical equipment in 100V environments. Featuring true online double-conversion technology, it ensures zero transfer time and pure sine wave output, protecting sensitive loads such as servers, network equipment, control systems, and telecommunications hardware.With a 1.5kVA / 1.0kW capacity and a 3U rack-mountable design, the FW-V10R-1.5K offers a space-saving solution that integrates easily into standard equipment racks. Intelligent monitoring, wide input voltage tolerance (AC85–144V), and robust battery management make it ideal for professional and industrial use.

  • The Mitsubishi FW-V10-5.0K is a high-performance uninterruptible power supply (UPS) designed for critical systems operating on 100V power. As part of Mitsubishi Electric’s FREQUPS FW-V Series, this tower-type UPS provides true online double-conversion protection, ensuring a seamless and clean power supply even under unstable grid conditions or during power outages.With a rated output of 5.0kVA / 3.5kW, the FW-V10-5.0K is well-suited for applications such as small server rooms, industrial control equipment, and communication systems. It features both terminal block and NEMA outlet outputs, along with intelligent monitoring via RS-232C and external I/O.

  • The Mitsubishi UPS FW-V10-3.0K is a compact, tower-style line-interactive UPS for 100 V environments like server racks, network closets, and control panels. Rated at 3.0 kVA/2.1 kW, it provides pure sine-wave output and switches to its VRLA battery in under 1 ms during power fluctuations (85–144 VAC, 47.5–63 Hz). The FW-V10-3.0K offers 10 minutes of backup at full load, six NEMA 5-15R outlets, three M4 terminals, RS-232C, USB-B, and alarm inputs, ensuring seamless power protection.

  • The Mitsubishi UPS FW-V10-2.0K is engineered to deliver enterprise‐grade reliability in a space‐constrained setting. Its line‐interactive inverter topology continuously monitors and corrects incoming voltage and frequency, so minor fluctuations are handled on the fly without ever tapping into battery power. Only when a significant anomaly occurs does the FW-V10-2.0K shift to battery mode in under one millisecond, preserving the integrity of sensitive equipment such as rack-mount servers, industrial PLCs, and network switches.

  • The Mitsubishi UPS FW-V10-1.5K is a compact, tower-style, line-interactive uninterruptible power supply engineered for small branch offices, network closets, and industrial control panels. Designed for reliable power protection, the FW-V10-1.5K delivers 1.5 kVA / 1.0 kW of pure sine-wave output and provides instant, zero-transfer “no-break” switching to battery when utility power is unstable.